Ranges: 0.6 bar up to 600 bar
Basic accuracy: ±0.5%
Sensor: ceramic thick film
Pressure port: G 3/4” (for flush diaphragm); G1/2ˮ; G1/4ˮ; 1/2ˮ NPT; 1/4ˮ NPT; M20x1.5; etc.
Pressure port materials: stainless steel (for abrasive media), plastic (for aggressive media)
Media temperatures: -10…+60 °C
Ambient temperatures: 0…+50 °C
Display: 4 ½ digits with backlight, min / max value, bargraph, units, 330° rotatable
Battery life: 1 year to 5 years
Ingress protection: IP 65
Features: configurable via buttons, including zero trim, auto-off, etc
OCTO 3410 digital pressure gauge is based on a ceramic oil free sensor to withstand aggressive(*) media. Optionally, plastic process connection is available for certain alkalis and acids. Flush ceramic diaphragm and the open port options are available for the viscous and/or abrasive media. Oil free dry pressure cell makes ANZ 3410 G suitable for environments with high oxygen levels and allows to measure gases with high O2 concentrations. Powered by 2xAA batteries, ANZ 3410 G provides up to a year of reliable readings of pressure updated twice every second in active mode, and up to 5 years in on-demand mode. For user convenience, the instrument has a backlight with auto-off feature. In addition to the current pressure reading, a multifunctional display shows minimum and maximum values since the last reset. User is able to trim zero and the full scale, select measurement units, decimal point position, adjust auto-off timeout.
(*) please consult the manufacturer for particular media compatibility